    IEC 60332-2-2 Vertical Flame Propagation Test for Single Wires or Cables: Spread of Flame Procedure

    Category:

    Electrical Wires


    IEC 60332-2-2 Standard Description

    IEC 60332-2-2 Tests on electric and optical fibre cables under fire conditions - Part 2-2: Test for vertical flame propagation for a single small insulated wire or cable - Procedure for diffusion flame

     

    IEC 60332-2-2 Standard Introduction

    The IEC 60332-2-2 test is part of the IEC 60332 series and is primarily used to determine the vertical flame propagation characteristics of single small insulated wires and cables. By conducting IEC 60332-2-2 testing, manufacturers and regulatory authorities can verify whether cables comply with specified fire safety requirements, thereby reducing the risk of fire spread in buildings and facilities.

     

     

    IEC 60332-1-3 Scope of Application

    Applicable to various power cables, optical fibre cables, and control and communication cables.

     

     

    IEC 60332-2-2 Sample Preparation

    A wire, cable, or optical fibre specimen with a length of (600 ± 25) mm shall be conditioned at (23 ± 5) °C and (50 ± 20)% relative humidity for at least 16 hours.

    Note: If the specimen surface is coated with paint or varnish, the test specimen shall be conditioned at (60 ± 2) °C for 4 hours.

     

    IEC 60332-2-2 Test Method

    (1) Sample Preparation:

     

    Sample Type

    Metallic conductor cable specimen

    Optical cable specimen

    Specimen Installation

    The sample is vertically fixed in the middle of the metal shield using a metal wire.

    The specimen is secured to two horizontal supports with metal wire.

    A force of 5 N/mm is applied to the lower portion of the specimen. 2 The load of

    -

    The distance from the load‑specimen connection point to the lower edge of the upper support shall be (550 ± 5) mm.

    The distance between the lower edge of the upper bracket and the upper edge of the lower bracket of the two horizontal supports for the fixed specimen shall be (550 ± 5) mm.

    -

    The distance between the lower edge of the upper bracket and the upper edge of the lower bracket of the two horizontal supports for the fixed specimen shall be (550 ± 5) mm.

    The specimen axis shall be perpendicular and positioned at the center of the metal enclosure, i.e., 150 mm from each side face and 225 mm from the rear face.

     

     

     

    (2) Blowtorch position

     

    Sample Type

    Metallic conductor cable specimen

    Optical cable specimen

    Specimen Installation

    The angle between the centerline of the blowtorch and the centerline of the specimen is (45±2)°.

    The horizontal distance between the centerline of the blowtorch nozzle and the specimen shall be (10 ± 1) mm.

    The intersection of the centerline of the blowtorch and the centerline of the specimen, under an applied load of 5 N/mm².

    -

    The distance between the intersection of the torch’s centerline and the specimen’s centerline and the applied load shall be (100 ± 10) mm.

    The distance between the intersection of the torch’s centerline and the specimen’s centerline and the upper surface of the lower support shall be (100 ± 10) mm.

    The distance between the intersection of the blowtorch’s centerline and the specimen’s centerline and the lower edge of the upper support shall not exceed 465 mm.

    The flame shall envelop the specimen.

     

    (3) Ignition Time

    The flame shall be applied to both metallic conductor cable specimens and optical fibre cable specimens for (20 ± 1) seconds.

    (4) Post-Test Cleaning

    After all combustion has ceased, wipe the specimen. If the original surface remains intact, removable soot and softening or deformation of non-metallic materials may be disregarded.

     

    IEC 60332-2-2 Basis for determination

    - Measure the distance between the lower edge of the upper support and the upper and lower boundaries of the charred section.
    - To determine the starting point of the charred section, press the cable surface gently with a sharp object (such as a knife blade). The point where the elastic surface becomes brittle and powdery is considered the beginning of the charred section.

     

    Available related cable testing services

    IEC 60332-3-21 Tests on electric cables under fire conditions - Part 3-21: Test for vertical flame spread of vertically-mounted bunched wires or cables; Category A F/R
    IEC 60332-3-22 Tests on electric cables under fire conditions - Part 3-22: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category A
    IEC 60332-3-23 Tests on electric and optical fibre cables under fire conditions - Part 3-23: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category 

    IEC 60332-2-2 Tests on electric and optical fibre cables under fire conditions - Part 2-2: Test for vertical flame propagation for a single small insulated wire or cable - Procedure for diffusion flame

    EN 50575 Power, control and communication cables - Cables for general applications in construction works subject to reaction to fire requirements

    EN 13501-6 Fire classification of construction products and building elements - Part 6: Classification using data from reaction to fire tests on power, control and communication cables

    GB/T 18380.13 Burning tests on electric and optical cables under flame conditions - Part 13: Test method for the determination of burning drips/particles by the vertical flame spread test for single insulated wires and cables

    IEC 60332-3-25 Tests on electric and optical fibre cables under fire conditions - Part 3-25: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category D

     

    SATISFY provides cable testing services under IEC 60332-2-2 fire exposure conditions, including Part 2-2: Vertical Flame Propagation Test for Single Small Insulated Wires or Cables - Diffusion Flame Procedure. Our services include diffusion flame testing, report interpretation, data analysis, and recommendations for corrective actions. For more information, please contact SATISFY customer service.